Station Grounding, Bonding & Block Diagram
Last Updated: YYYY-MM-DD
Primary Objective: Document lightning protection, single-point ground bonding, and RF/AC interconnect paths for safety, maintenance, and insurance records.
Station Block Diagram
Replace or supplement this ASCII diagram with an exported image (PNG/SVG) from Draw.io, KiCad, or Inkscape uploaded via the Media Manager.
[ Antennas ]
│
▼ (Coax Feedlines: LMR-400)
[ Outdoor Entry Panel ] ───► ( #6 AWG Solid Cu ) ───► [ Entrance Ground Rod ]
│ (PolyPhaser Arrestors) │
▼ │ ( #2 AWG Buried Bond )
[ Shack Coax Switch / Patch Panel ] ▼
│ [ Utility AC Service Ground ]
├──► [ HF Transceiver ] ◄───► [ Tuner / Amp ]
│ │ │
│ ▼ (1" Tinned Copper Braid)
└──► [ Shack Single-Point Ground Busbar ] ◄─── [ 12V DC Power Supply ]
Outdoor Grounding & Lightning Protection
| Component | Specification / Model | Location & Notes |
| Coax Entry Panel | e.g., KF7P 8×8 Aluminum NEMA Box | Exterior wall, 2 ft above grade, adjacent to shack |
| Lightning Arrestors | e.g., PolyPhaser IS-50UX-C0 (HF/VHF) | Mounted directly to grounded bulkhead plate inside entry box |
| Entrance Ground Rod | e.g., 8 ft x 5/8“ Copper-Clad Steel | Driven 2 ft from foundation directly below entry panel |
| Inter-System Bond | e.g., #2 AWG Bare Solid Copper | Buried 12” deep; bonds entrance rod to main house AC ground rod |
| Disconnect Procedure | Manual disconnect + shorting plugs | Coax jumpers disconnected from shack bulkhead during severe storms |
Indoor Single-Point Ground (SPG) & RF Bonding
All chassis grounds are bonded to a central copper busbar behind the operating desk to prevent ground loops and minimize shack RFI.
| Equipment / Chassis | Bonding Conductor | Connection Point |
| Shack Ground Busbar | 1/4“ x 2” x 18“ C110 Copper Bar | Mounted to rear of desk on standoff insulators; tied to entry panel via #4 AWG |
| HF Transceiver | 1” Tinned Flat Copper Braid (18“) | Rear chassis GND lug ──► Shack Busbar |
| Antenna Tuner / Amp | 1” Tinned Flat Copper Braid (24“) | Rear chassis GND lug ──► Shack Busbar |
| 12V DC Power Supply | #10 AWG Green Stranded Wire | Chassis ground screw ──► Shack Busbar (DC negative floating) |
| AC Surge Protection | e.g., Tripp Lite Isobar Ultra | Plugged into dedicated 20A shack breaker; feeds radio PSU & PC |
| Common-Mode Chokes | e.g., Fair-Rite Type 31 Toroid (12 turns) | Installed at coax entry to shack and on USB/CAT control cables |
Maintenance & Inspection Log
Regular checks ensure outdoor connections remain tight and corrosion-free.
| Date | Inspection Item | Findings & Action Taken |
| YYYY-MM-DD | Exterior Cadweld / Clamp Joints | Inspected clamps at entrance rod; applied Noalox anti-oxidant compound. |
| YYYY-MM-DD | Arrestor Gas Discharge Tubes | Verified continuity and DC blocking on PolyPhaser units; all nominal. |
| YYYY-MM-DD | Indoor Busbar Torque Check | Checked all brass hardware on shack copper busbar; tightened 2 lugs. |